This User Manual details the product features, application scope, installation, use, maintenance and other contents of NDC3(N、GV)-40(11、11S)/50(11、 11S)/65(11、11S)/80(11、 11S)/95(11、11S) AC contactor.
This manual describes the NDC3(N、GV) series AC contactors with rated operating currents from 40A to 95A under AC-3 at 415V. The contactors are designed for AC 50/60Hz circuits with a rated insulation voltage of 1000V, used for frequent starting and control of AC motors. Reversible versions allow forward/reverse motor control and plug braking. The document applies to standard ambient temperatures of -25°C to +60°C and altitudes up to 3000m.
The manual provides wiring diagrams, connection capacities for main and auxiliary terminals, coil voltage ranges (24-440V AC, 24-250V DC), pull-in and release characteristics, power consumption, outline and mounting dimensions for each frame size, accessory options (NF1, NF2 auxiliary contacts, NS1 time-delay blocks), accessory installation procedures, and ordering specifications. This manual is written in Chinese.
| Rated insulation voltage | 1000V |
|---|---|
| Rated operating voltage (AC-3) | 415V |
| Rated operating current (AC-3) | 40-95A |
| Operating frequency | 50/60Hz |
| Standard operating ambient temperature | -25°C to +60°C |
| Ultimate operating ambient temperature | -40°C to +70°C |
| Storage temperature | -60°C to +80°C |
| Normal operating altitude | ≤3000m |
| Ultimate operating altitude | ≤5000m |
| Pollution grade | Grade 3 |
| Installation orientation | Vertical, standard ±5°, ultimate ±30° |
| Mounting method | TH35/TH75 DIN rail or screw |
| Control voltage range (AC) | 24-440V 50/60Hz |
| Control voltage range (DC) | 24-250V |
| Pull-in voltage | 0.85Us-1.1Us |
| Release voltage (AC) | 0.2Us-0.6Us |
| Release voltage (DC) | 0.1Us-0.6Us |
| Pull-in power (40-80A models) | ≤200VA / ≤60W |
| Hold power (40-80A models) | 15VA / 3W |
| Pull-in power (95A model) | ≤300VA / ≤90W |
| Hold power (95A model) | 26VA / 3W |
| Main terminal wire capacity (40-80A) | 1-35 mm² hard, 1-35 mm² soft, 1-25 mm² cold-pressed |
| Main terminal wire capacity (95A) | 2.5-70 mm² hard, 2.5-70 mm² soft, 2.5-50 mm² cold-pressed |
| Auxiliary/coil terminal wire capacity | 1-4 mm² hard, 0.75-2.5 mm² soft |
The standard operating ambient temperature is -25°C to +60°C.
It can be mounted on TH35 or TH75 standard DIN rails or fixed with screws.
AC 24-440V at 50/60Hz and DC 24-250V.