Liangxin NDM2Z Series DC Molded Case Circuit Breaker Product Manual

NDM2Z Series MCCB Product Manual of Shanghai Liangxin Electrical Co., Ltd.


Liangxin NDM2Z Series DC Molded Case Circuit Breaker Product Manual - cover page
Brand
Liangxin
Category
switch
Document type
User Manual
Language
Chinese
Pages
20
File format
PDF
File size
1.1 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
4CAC59119CB2692FEA779576A2878B42

About this manual

The NDM2Z Series DC molded case circuit breaker is divided by function into NDM2Z(X) and NDM2ZB. It is intended for DC power circuits with a rated operational voltage of DC250V and a rated operational current up to 800A, to distribute power and protect circuits and power equipment. The breaker provides overload and short-circuit protection; NDM2ZB also has short-circuit short-delay protection, and the breaker has an isolating function.

This bilingual product manual covers application scope, model designation, main technical parameters, standard working conditions, wiring method, outline and installation dimensions, mounting method, accessories, use and maintenance, and notices. It also lists GB14048.1-2006, GB14048.2-2008, GB14048.4-2003 and GB14048.5-2001 as standards met by the product. This manual is written in Chinese.

What's inside

  • Application scope
  • Model and implication
  • Main technical parameters
  • Stand working conditions
  • Wiring Method
  • Shape dimension & Dimension
  • Mounting Method
  • Accessory
  • Application & Maintenance
  • Notices

Specifications

Rated operational voltageDC 250 V
Rated operational currentUp to 800 A
Shell frame level63, 125, 250, 400, 630
Pole number2 or 3
Ambient temperature-35 to +70 °C
Storage ambient temperature-40 to +75 °C
Altitude≤2000 m
Pollution degree3
Relative humidity at 40 °CNot exceeding 50%

Frequently asked questions

What is the rated operational voltage and current of the NDM2Z Series?

The breakers are intended for DC power circuits with a rated operational voltage of DC250V and a rated operational current up to 800A.

What protections does the breaker provide?

The breaker provides overload and short-circuit protection.

What additional protection does NDM2ZB provide?

NDM2ZB further has short-circuit short-delay protection.

Does the breaker have an isolating function?

Yes. The breaker has an isolating function.