NDM2Z Series MCCB Product Manual of Shanghai Liangxin Electrical Co., Ltd.
The NDM2Z Series DC molded case circuit breaker is divided by function into NDM2Z(X) and NDM2ZB. It is intended for DC power circuits with a rated operational voltage of DC250V and a rated operational current up to 800A, to distribute power and protect circuits and power equipment. The breaker provides overload and short-circuit protection; NDM2ZB also has short-circuit short-delay protection, and the breaker has an isolating function.
This bilingual product manual covers application scope, model designation, main technical parameters, standard working conditions, wiring method, outline and installation dimensions, mounting method, accessories, use and maintenance, and notices. It also lists GB14048.1-2006, GB14048.2-2008, GB14048.4-2003 and GB14048.5-2001 as standards met by the product. This manual is written in Chinese.
| Rated operational voltage | DC 250 V |
|---|---|
| Rated operational current | Up to 800 A |
| Shell frame level | 63, 125, 250, 400, 630 |
| Pole number | 2 or 3 |
| Ambient temperature | -35 to +70 °C |
| Storage ambient temperature | -40 to +75 °C |
| Altitude | ≤2000 m |
| Pollution degree | 3 |
| Relative humidity at 40 °C | Not exceeding 50% |
The breakers are intended for DC power circuits with a rated operational voltage of DC250V and a rated operational current up to 800A.
The breaker provides overload and short-circuit protection.
NDM2ZB further has short-circuit short-delay protection.
Yes. The breaker has an isolating function.