Liangxin NDR2-38 Thermal Overload Relay User Manual

Liangxin NDR2-38 series bimetal thermal overload relay user manual: model designation, technical data, wiring, reset, dimensions, mounting and ordering.


Liangxin NDR2-38 Thermal Overload Relay User Manual - cover page
Brand
Liangxin
Category
electric relay
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
472 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
16FE38C17CE15A97B291C14AB46A9EA0

About this manual

This is the third edition (dated 20181015) of document NDT510071, the user manual for the Liangxin NDR2-38 series bimetal thermal overload relay. It covers the scope of application, model designation, structure, technical parameters, action characteristics, operating environment, wiring, use instructions, outline and mounting dimensions, mounting methods, precautions and ordering information.

The NDR2-38 is used for overload and phase-failure protection of AC motors in 50 Hz or 60 Hz circuits with a rated operating voltage up to 690 V and a setting current range of 0.1 to 38 A. It can be plugged directly onto NDC1 contactors for combined mounting, or mounted separately on a mounting base with screws or on a DIN rail. The manual includes tables of current setting ranges, fuse selection, terminal wire capacity, action characteristics and mounting dimensions. This manual is written in Chinese.

What's inside

  • 适用范围与用途
  • 型号说明
  • 结构形式
  • 技术参数
  • 动作特性
  • 接线端子连接导线的能力
  • 工作环境
  • 接线方式(接线图)
  • 使用说明
  • 外形尺寸和安装尺寸

Specifications

Current range Ie0.1~38 A
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp6 kV
Trip class10A
Temperature compensation range-5~+40 ℃
Enclosure protection gradeIP20
Auxiliary contact1NO+1NC
Conventional thermal current Ith5 A
StandardsIEC60947-4, GB/T 14048.4
Operating temperature-5~+40 ℃ (storage -25~+55 ℃)

Frequently asked questions

What is the NDR2-38 thermal overload relay used for?

It is used for overload and phase-failure protection of AC motors in 50 Hz or 60 Hz circuits with a rated operating voltage up to 690 V and a rated current of 0.1 to 38 A.

How can the NDR2-38 be mounted?

It can be plugged directly onto an NDC1 contactor for combined mounting, or mounted separately on an independent mounting base with screws or on a DIN rail.

What reset state does the relay have when delivered?

The relay is set to manual reset at the factory; in manual reset mode, press the manual reset button about 5 minutes after tripping.

What are the ambient temperature limits for operation?

The operating ambient temperature is -5 to +40 ℃ and the storage temperature is -25 to +55 ℃.

Download PDF (472 KB)