This product is a 1P+N circuit breaker, suitable for use in homes, factories and other places. The product has overcurrent, short circuit, leakage protection and other functions, safe and reliable.
This document is a product introduction manual for the Liangxin NDB1-40, a 1P+N small circuit breaker. It summarizes the product profile, features, application scope, technical characteristics, specification and model description, technical parameters, temperature correction and high-altitude derating tables, trip curve, accessories, dimensions and wiring diagram.
The manual lists a rated voltage of AC230/240 V, rated currents from 2 A to 40 A, B/C/D trip characteristics, a 6 kA rated short-circuit breaking capacity, and compliance with GB 10963.1 and IEC 60898-1. It also gives environmental limits, protection and pollution degrees, mounting details, accessory forms and installation dimensions. This manual is written in Chinese.
| Rated voltage | AC230/240 V |
|---|---|
| Rated current | 2, 4, 6, 10, 16, 20, 25, 32, 40 A |
| Trip characteristic | B: 3In-5In, C: 5In-10In, D: 10In-14In |
| Standards | GB 10963.1; IEC 60898-1 |
| Mounting | TH35 mm DIN rail |
The listed rated currents are 2, 4, 6, 10, 16, 20, 25, 32, and 40 A.
The available trip characteristics are B (3In-5In), C (5In-10In), and D (10In-14In).
The manual references IEC 60898-1.