This manual is for guidance only and must be read in conjunction with the Installation and Servicing instructions supplied with the boiler.
The document covers flue terminal positioning requirements with minimum spacing distances from openings, gutters, eaves, balconies, and other structures as per BS5440-1 2008. It lists flue accessory kits such as telescopic and horizontal flue terminals, roof flue kits, powered vertical flue kits, high level flue outlet kits, balcony flue outlet kits, and soffit kits, each with Ideal part numbers.
Maximum permissible flue lengths are specified for different boiler outputs: 9 metres for 24-26 kW Combi appliances, 8 metres for 30-32 kW, and 6 metres for 35-38 kW; for System and Heat models, 9 metres for 15-24 kW and 8 metres for 30 kW. Powered vertical flue allows up to 7.5 metres concentric flue plus 17 m flue pipe. Equivalent resistance values for 90° and 45° elbows are given, and minimum horizontal flue lengths are noted.
| Maximum horizontal concentric flue length (24-26 kW Combi) | 9 metres minus any flue kit options or bends |
|---|---|
| Maximum horizontal concentric flue length (30-32 kW Combi) | 8 metres minus any flue kit options or bends |
| Maximum horizontal concentric flue length (35-38 kW Combi) | 6 metres minus any flue kit options or bends |
| Maximum powered vertical flue length (24-38 kW Combi) | 7.5 metres concentric flue and 17 m flue pipe only |
| 90° elbow equivalent flue length resistance | 1 metre |
| 45° elbow equivalent flue length resistance | 0.6 metre |
| Minimum horizontal flue length (telescopic B pack) | 400 mm |
| Minimum horizontal flue length (horizontal flue terminal 600 mm B pack) | 285 mm |
The maximum horizontal flue length is 9 metres minus any flue kit options or bends.
The kit comprises a flue elbow, a 60 mm flue exit elbow, a 60 mm horizontal flue exit, and a 60 mm x 500 mm flue outlet extension pipe.
The minimum horizontal flue length is 400 mm measured from the centre line of the turret to the outside of the wall terminal.
The 90° elbow kit adds an equivalent flue length resistance of 1 metre.