Infrared Refrigerant Leak Detector CFCs, HFCs, HCFC Blends, and HFO-1234YF Operator’s Manual
The Bacharach Tru Pointe IR is a hand-held refrigerant gas detector that uses infrared technology to detect CFCs, HFCs, HCFC blends, and HFO-1234YF in HVAC/R applications. Features include sensitivity below 0.1 oz/yr, adjustable squelch, Background Mode, LED bar graph display with audible feedback and mute, peak reading, and a rechargeable lithium-ion battery.
Additional features include a 30-second self-test and calibration at start-up, dual charging capabilities, a rugged housing with rubber boot and magnetic clip, a 15-inch flexible probe with extensions, a replaceable filter, and a molded plastic carrying case. The manual covers safety precautions, lithium battery care, components, specifications, charging, button and LED operation, sensitivity settings, probe selection, leak detection, filter replacement, and replacement parts and accessories.
| Type of detector | Locating leak detector (type C) |
|---|---|
| Refrigerants | HFC, CFC, HCFC, HFO-1234YF and blends |
| Sensitivity level | <0.1 oz/yr (<3 g/yr) |
| Output signal | Instantaneous with audio and visual indicators |
| Dimensions (H x L x W) | 1.25 in x 7.5 in x 2.25 in (3.18 cm x 19.05 cm x 5.72 cm) |
| Weight | 15 oz (0.4 kg) |
| Environment temperatures | Operation: 32 F to 122 F (0 C to 50 C); Storage: -4 F to 140 F (-20 C to 60 C) |
| Sensing element | Enhanced infrared photo optics |
| Sensor life | Approximately 10 years |
| Battery type | Lithium-ion; 3.7 V, 1800 mAH rechargeable |
| Battery charge | 8 hours continuous use before recharge |
| Battery recharge time | Approximately 3 hours |
| Battery indicator | Alert LED is on when 1 hour of battery life remains |
| Auto off | After 10 minutes of inactivity |
| Compliance | Exceeds requirements of SAE J1627, J2791, and J2913; CE pending; EN 14624:2012 |
| Patent | 7,022,993 |
| Response time | < 1 second |
| Recovery time | <2 seconds |
| Zeroing time | < 2 seconds |
| Calibration | None required (auto calibration) |
| Fixed probe lower detection limit | 0.5 g/yr (0.02 oz/yr) |
| Moving probe lower detection limit | 1.0 g/yr (0.04 oz/yr) |
| Contamination lower detection limit | 3.5 g/yr (0.12 oz/yr) |
| Repeatability | 100% |
| Probe | 15-inch flexible probe with 9-inch flexible extension and 9-inch rigid extension |
It detects CFCs, HFCs, HCFC blends, and HFO-1234YF in HVAC/R applications.
No calibration is required because it automatically adjusts to ambient conditions.
The sensitivity level is less than 0.1 oz/yr (less than 3 g/yr).
The lithium-ion battery provides 8 hours of continuous use before recharge, and recharging takes approximately 3 hours.