Liquiphant FailSafe with Nivotester FailSafe is a safety-rated level measuring system for liquids.
This document is a functional safety manual for the Liquiphant FailSafe FTL80/81/85 level limit measuring system. It covers Version I with Nivotester FailSafe FTL825 and Version II using only the Liquiphant FailSafe sensor for minimum or maximum level monitoring of liquids in safety systems according to IEC 61508 Edition 2.0.
It describes system structure, permitted device types, safety requirements and boundary conditions, installation, operation, device configuration, maintenance, proof testing, repairs, return, commissioning or proof test protocols, and the certificate.
| Safety function | Point level detection (minimum or maximum) |
|---|---|
| Version I output | Two safety contacts (terminals 13/14 and 23/24) |
| Version II output | 4 to 20 mA analog signal |
| MIN mode OK current | 18.5 mA |
| MAX mode OK current | 13.5 mA |
| MIN mode demand current | 9.0 mA |
| MAX mode demand current | 6.0 mA |
| Fault alarm current | < 3.6 mA |
| Short-circuit alarm current | > 21.0 mA |
| LIVE signal | 0.25 Hz square wave, ±0.5 mA amplitude |
| Valid firmware version | as of 01.00.00 |
| Valid hardware version | as of 01.00 (electronics) |
| SIL capability | up to SIL 3 according to IEC 61508 Edition 2.0 |
The measuring system's safety function is point level detection, implemented as maximum or minimum point level detection.
Version I uses Liquiphant FailSafe with Nivotester FailSafe, and Version II uses only Liquiphant FailSafe.
It reports status OK with a nominal current of 18.5 mA, including the LIVE signal.
The manual includes proof test procedures and commissioning or proof test protocols for Version I and Version II.