This document is the installation manual for the P2000 Security Management System VPN/DSL Security Option.
This installation manual describes how to install and configure the VPN/DSL Security Option for the Johnson Controls P2000 Security Management System. Document 24-10515-188 Revision A, dated October 2010, it covers IPSEC parameters such as the P2000 server IP address and the VPN router WAN and LAN IP addresses, along with hardware installation steps.
The manual includes installation and configuration procedures for the NetScreen-5XT, Linksys BEFVP41, and Linksys BEFSX41 VPN routers, plus instructions for installing the Digi EtherLite device (for S320 connections) and the Digi One SP (for S321 connections). It also reproduces the Underwriters Laboratories compliance verification sheet for UL 1076 listed systems and ends with a glossary appendix.
| UL listing | UL 1076 Proprietary Burglar Alarm Units and Systems |
|---|---|
| Maximum number of panels | 1000 |
| Operating environment temperature | 13 - 35 C (55 - 95 F) |
| Panel poll interval (UL requirement) | must not exceed 90 seconds |
| Host poll delay (UL requirement) | must not exceed 200 seconds |
| VPN router for line security | NetScreen NS-5XT-X0X 4-Port VPN router |
A NetScreen Model NS-5XT-X0X 4-Port VPN router is required, and the server and router must use an encryption method with an Authentication Header and Triple-DES (3DES) or better that is NIST certified.
The temperature controlled environment for the network hub, router, serial port server and host computer must be maintained between 13 - 35 C (55 - 95 F) by the HVAC system, with 24-hour standby power for the HVAC.
The maximum number of panels that may be connected to the P2000 or P2K system is 1000.
The system uses the Digi International Model Digi One SP converter or the B&B Electronics Model 485OT9L RS232-to-RS485 converter to communicate with S321-DIN controllers.