This test transformer adopts a new production process, with greatly improved technical performance, and is suitable for use in field work and laboratory working conditions.
This manual describes the YDQ series gas-filled (inflatable) light test transformer, a test device for power equipment inspection and preventive testing. Compared with traditional oil-immersed test transformers, the SF6 gas-insulated design is 20%-60% lighter (depending on voltage and capacity), causes no oil pollution, and a single unit can reach voltage levels up to 300kV with very low partial discharge.
The manual explains the structure of the YDQ, YDQ(JZ) and YDQ(C) variants, the working principle of AC and rectified DC high-voltage output, control wiring diagrams, test site layouts, operating procedures, safety precautions, maintenance including SF6 gas refilling, and the rated operating conditions and allowed running times of the transformer. This manual is written in Chinese.
| Max single-unit voltage | 300kV |
|---|---|
| Weight reduction vs oil-immersed type | 20%-60% |
| Partial discharge | below 2Pc at rated voltage |
| Factory gas pressure | 0.4-0.5MPa |
| Max gas refill pressure | 0.55MPa |
| Ambient temperature range | -20°C to +40°C |
| Max relative humidity | 85% at 25°C |
| Continuous running time at rated load | max 30 minutes |
No more than half an hour continuously, with intervals of 5-10 times the working time for cooling; at two-thirds of rated voltage and current it may run continuously.
The power-frequency high voltage is rectified by a high-voltage silicon stack and filtered by a stabilizing capacitor, giving DC whose amplitude is twice the RMS AC value.