This paper describes the key parameters to be considered for the selection of inverter transformers, along with various recommendations based on lessons learnt.
The paper presents generic guidelines for selecting inverter transformers used at the output of inverters in utility-scale photovoltaic plants. It describes terminology, recommends sizing the transformer according to the inverter reference load cycle and correlating it with temperature rise in line with IEC 60076-7, and discusses PCB-free mineral oil, dielectric breakdown voltage, and component and unit codes and standards.
It also explains magnetizing inrush and the effects of harmonics on transformer heating and insulation life. For harmonic currents above 5% of rated current, it says the heating effect should be evaluated using IEEE C57.110-1998.
| Recommended transformer oil | PCB free, polycyclic, aromatic, hydrocarbon free mineral oil in line with IEC 60296 |
|---|---|
| Dielectric breakdown voltage, new unused oil | 30 kV or more |
| Dielectric breakdown voltage after laboratory vacuum filtering | 70 kV minimum |
| In-service oil testing frequency | At least once a year |
| Harmonic current evaluation threshold | 5% of the transformer's rated current |
| Transformer sizing reference | Inverter reference load cycle, correlated with temperature rise in line with IEC 60076-7 |
| Harmonic heating evaluation standard | IEEE C57.110-1998 |
The recommended oil is PCB free, polycyclic, aromatic, hydrocarbon free mineral oil in line with IEC 60296.
For in-service equipment, it is recommended to test the oil at least once a year.
It must have a dielectric breakdown voltage of 30 kV or more, determined using the IEC 60156 test method.
The heating effect should be evaluated by applying the methodology contained in IEEE C57.110-1998.