People Electric LMK2-0.66 Current Transformer User Manual

User manual for the People Electric LMK2-0.66 indoor current transformer, covering installation, use, technical parameters, transport and storage.


People Electric LMK2-0.66 Current Transformer User Manual - cover page
Brand
People Electric
Category
transformers
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
1.4 MB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
1160A6F55C9F67F49ADDCB80DF37646E

About this manual

This is the Chinese instruction manual for the People Electric LMK2-0.66 indoor current transformer, a busbar-type (母排式) current transformer for circuits with a rated voltage of 0.66 kV and below and a rated frequency of 50(60) Hz. The document states that the product complies with GB/T 20840.2, and gives the conditions of use, the meaning of the model code, the structure and working principle, and the main technical parameters such as rated secondary current, rated burden and accuracy class.

The manual then covers outline, through-hole and mounting dimensions with tables for each size (LMK2-0.66/30 up to /150 and the L versions), the two mounting methods using M5 screws or busbar clamping plates, the use of the P1/P2 and S1/S2 terminals, and how the number of primary turns through the window changes the current ratio. It closes with transport and storage precautions, the warranty terms, ordering information and a packing list, and carries a conformity certificate page. This manual is written in Chinese.

What's inside

  • General Description and Main Applications
  • Operating Environment Conditions
  • Model Designation
  • Structure and Working Principle
  • Technical Parameters
  • Outline, Through-Hole and Mounting Dimensions
  • Installation
  • Use
  • Transportation and Storage
  • Warranty and Ordering Information

Specifications

Rated voltage0.66 kV
Rated frequency50(60) Hz
Rated secondary current1 A
Power factor0.8
Rated secondary burden2.5 VA, 5 VA, 10 VA, 15 VA
Accuracy class1.0, 0.5, 0.2, 0.5S, 0.2S
Insulation resistance (secondary to earth)>20 MΩ
Power-frequency withstand voltage (secondary to earth)3 kV
Ambient temperature-5 to 40 °C
Relative humidity≤80%
Altitude≤1000 m
StandardGB/T 20840.2

Frequently asked questions

Which standard does the LMK2-0.66 current transformer comply with?

The manual states that the product complies with GB/T 20840.2.

What are the rated voltage and rated frequency?

The rated voltage is 0.66 kV and the rated frequency is 50(60) Hz.

How is the current transformer mounted?

Two methods are described: fixing it to a mounting plate or beam with M5 screws or bolts, or clamping it onto the current busbar with clamping plates and fixing bars. It may be installed vertically or horizontally.

What is the warranty period?

The company repairs or replaces the product free of charge within eighteen months from the production date or twelve months from the invoice date, provided the storage and use conditions are met.