Johnson Controls A421 Series Electronic Temperature Controls with Cycle Timer Installation Guide

The A421 Series Electronic Temperature Controls are single-stage, electronic temperature controls with a single- pole, double-throw (SPDT) output relay. A421 Controls feature a backlit LCD with adjustable brightness and three-button touchpad interface that


Johnson Controls A421 Series Electronic Temperature Controls with Cycle Timer Installation Guide - cover page
Brand
Johnson Controls
Category
Other Electronics
Document type
Installation Guide
Language
English
Pages
14
File format
PDF
File size
918 KB
Published
11 November, 2023
Updated
11 November, 2023
MD5 checksum
72088526CE1A84D4BEAFAB9BBAF25F37

About this manual

Johnson Controls A421 Series Electronic Temperature Controls with Cycle Timer are single-stage electronic temperature controls with an SPDT output relay. They feature a backlit LCD with adjustable brightness, a three-button touchpad interface, an LED showing output relay status, sensor offset capability, and restricted user adjustment. The temperature control range is -40°F to 212°F (-40°C to 100°C). Controls are available in Type 1 (NEMA), IP20 (CE) high-impact plastic enclosures or Type 4X (NEMA), IP66 (CE) watertight, corrosion-resistant surface-mount enclosures.

The A421 Control with Cycle Timer is a free-cooling, duty-cycle ventilation control used in agricultural and related applications. This installation guide covers A99 Series temperature sensors, mounting, wiring, sensor cable lengths, and related precautions. Each control includes an A99 Series temperature sensor, and the controls require an A99 sensor.

What's inside

  • Applications
  • Parts included
  • A99 Series Temperature Sensors
  • Mounting
  • Wiring
  • Technical specifications
  • Ordering information
  • Troubleshooting
  • Dimensions

Specifications

Temperature control range-40°F to 212°F or -40°C to 100°C
Output relaySingle-pole, double-throw (SPDT)
Enclosure optionsType 1 (NEMA), IP20 (CE) high-impact plastic or Type 4X (NEMA), IP66 (CE) watertight, corrosion-resistant
A99 sensor resistance at 77°F (25°C)1,035 ohms
Maximum sensor cable length, 16 AWG500 ft (150 m)
Cycle timer functionFree-cooling, duty-cycle ventilation control

Frequently asked questions

What temperature sensor does the A421 control require?

The A421 Controls require an A99 Series temperature sensor, and each control includes an A99 sensor.

Can the A99 sensor leads be extended?

Yes, the sensor leads can be extended in the field; see Table 1 for recommended wire sizes and lengths.

What is the temperature control range?

The temperature control range is -40°F to 212°F or -40°C to 100°C.

How can an A99 sensor be tested?

Disconnect the sensor from the control and measure the resistance between the sensor leads; it should be 1,035 ohms at 77°F (25°C) and 855 ohms at 32°F (0°C).

Download PDF (918 KB)