This document describes the application guide for fire alarm control panel LT-1091.
This Releasing Application Guide, Rev. 2.2 dated July 2018, documents the FX-3500RCU fire alarm control panel for releasing applications. It describes operating the panel, configuring hazard zones, counting zone types, abort types, configurable timers, and hazard zone states.
The guide covers releasing circuit wiring, including Class B/Style Y wiring, and typical pre-action/agent release and deluge applications with single, double, triple, and 2-input activation. FM applications must have Class A initiating circuits only and 90-hour battery standby operation; only UL/ULC listed manual abort and manual release switches, such as the Mircom SS-2004, are permitted.
| Release Delay Timer (RDT) maximum | 60 seconds |
|---|---|
| Soak Delay Timer (SDT) maximum | 600 seconds |
| Manual Release Delay Timer (MRDT) maximum | 60 seconds |
| FM initiating circuits | Class A initiating circuits only |
| FM battery standby | 90 hours |
| Releasing circuit module compatibility | M500S and MIX-M500SAP supervised output modules |
| Solenoid supervision module | MP-3500R/W Solenoid EOL |
The maximum value for the Release Delay Timer (RDT) is 60 seconds.
The maximum value for the Soak Delay Timer (SDT) is 600 seconds.
No, manual release cannot be aborted once it has been initiated.
FM applications must have Class A initiating circuits only and 90-hour battery standby operation.