This manual describes how to use the TC4S-24R temperature controller.
This is a short Portuguese quick-parameterization sheet for Autonics TC4S temperature controllers, naming the TC4S-14R model and the TC4S-24R version with two alarms. It shows how to enter parameter 1 (MODE for 2 seconds) and parameter 2 (MODE for 4 seconds), and how to leave the parameter by pressing MODE for 3 seconds, plus the keyboard lock function and the key combination that enables or disables the main output and the alarm output during operation.
The sheet lists the settings grouped in the two parameter levels: sensor type (thermocouple K or J, RTD PT100), indication unit, sensor correction, display update time, control cycle time of 0.5 to 120.0 seconds (changed to 2.0 seconds with SSR output), six alarm modes with alarm hysteresis and deviation, heating or cooling action, relay or voltage (SSR) output with zero-cross or random-cross phase control, and the proportional band, integral time and derivative time adjustments. It also describes a percentage setting that keeps the main output switching between ON and OFF if the sensor breaks. This manual is written in Portuguese.
| Control cycle time | 0.5 to 120.0 seconds |
|---|---|
| Control cycle time with SSR output | 2.0 seconds |
| Alarm modes | 6 modes |
| Supported sensors | Thermocouple K, thermocouple J, RTD PT100 (DIN) |
| Proportional band | 0.1 to 999.9 ºC |
| Integral time | 0 to 9999 seconds |
| Derivative time | 0 to 9999 seconds |
| Hysteresis | 1 to 100 ºC |
| Sensor-break output percentage | 0.0 to 100.0% of the cycle time |
| Alarm 2 deviation | Available only on the 2-alarm controller (TC4S-24R) |
| Output types | Relay output or voltage output (SSR) |
Press MODE for 2 seconds to access parameter 1, and press MODE for 3 seconds when you are finished.
Press MODE for 4 seconds to access parameter 2, then press MODE for 3 seconds to exit.
There are 6 different alarm operating modes; the most used one is described in the full manual.
A percentage of the cycle time can be set so the main output switches ON and OFF according to that percentage; for example, with T set to 10 s and 50%, the output stays on 5 seconds and off 5 seconds.
Thermocouple types K and J and RTD PT100 sensors are listed for the controller.