The Siemens SICAM P35 and P36 three-phase electronic multifunctional electric energy meter is a power meter that integrates measurement recording, energy measurement, remote signaling and control, large-screen LCD display and network communication functions.
This manual (V1.5) from Siemens Power Automation describes the SICAM P35 and P36 three-phase electronic multifunction energy meters, which combine measurement and recording, energy metering, remote signaling and control, a large LCD display and network communication in one instrument. It covers technical specifications, functions, operation and display, installation and wiring, communication, use and maintenance, model and ordering numbers, and after-sales service.
The meters measure voltage, current, power, power factor and frequency, meter active and reactive energy, and offer an RS-485 port supporting Modbus-RTU and DL/T645 protocols, with optional digital inputs and relay outputs. They are intended for substation and distribution automation, industrial control and automation, energy management systems and residential power monitoring. This manual is written in Chinese.
| Wiring types | Three-phase three-wire, three-phase four-wire, single-phase |
|---|---|
| Reference voltage | AC380V, AC220V, AC100V, AC57.7V |
| Voltage measurement range | 10V–264V phase voltage, max 400V |
| Rated current | 1A, 5A |
| Current measurement range | 0.015–6A, max 9A |
| Power accuracy | 0.5% |
| Frequency measurement range | 45 Hz–65 Hz, accuracy 0.2% |
| Active energy accuracy class | 0.5S |
| Reactive energy accuracy class | Class 2 |
| Pulse output | 2 energy pulse outputs (active and reactive), optocoupler isolated, 4000V RMS |
| Digital outputs (optional) | 2 relay outputs, normally open, AC 250V/3A, DC 30V/3A |
| Digital inputs (optional) | 4 dry-contact inputs, optocoupler isolated, 4000V RMS |
| Communication | RS-485, two-wire half-duplex, 600bps–38400bps, Modbus-RTU and DL/T-645 |
| Operating temperature | -25°C to +60°C (limit -35°C to +70°C) |
| Power supply | AC or DC, 40V–420V max input, ≤1W / 2VA |
| Dimensions | 96×96×95 mm, cutout 92×92 mm, approx. 450 g |
| Protection rating | IP53 |
The RS-485 port supports the Modbus-RTU and DL/T645 protocols at 600bps to 38400bps.
Up to 6 groups of limit alarm parameters can be set simultaneously, each monitoring one of the voltage, current, power, power factor or frequency values.
Programming mode is valid for 10 minutes by default after the keys are pressed, and it expires when power is lost.
After the set number of wrong attempts (factory default 5), parameter setting is locked for a set time (factory default 60 minutes).