ifm KG (M18) Capacitive Sensor Operating Instructions

The KG (M18) capacitive sensor is a sensor for detecting metal objects. It features a detection range of up to 8 mm, a short response time of just 1 ms, high resistance to interference, easy installation without the need for special tools, and is suitable for a variety of industrial applications.


ifm KG (M18) Capacitive Sensor Operating Instructions - cover page
Brand
ifm
Category
sensor
Document type
User Manual
Language
Chinese
Pages
11
File format
PDF
File size
1 MB
Published
06 November, 2023
Updated
06 November, 2023
MD5 checksum
836A3B42B773269BC84E009EE21F73E3

About this manual

This document is the operating instructions for the ifm KG (M18) capacitive sensor used to monitor liquid levels and bulk materials. It describes installation, electrical connection, operating and display elements, setting procedures, IO-Link communication, operation and maintenance.

The sensor can be adjusted with its programming button, including basic empty adjustment, full adjustment, improved basic empty adjustment and lock/unlock functions. It also explains LED indications and disposal guidance. This manual is written in Chinese.

What's inside

  • Reading instructions
  • Safety instructions
  • Function and characteristics
  • Installation
  • Electrical connection
  • Operation and display elements
  • Setting
  • Basic empty adjustment
  • Full adjustment
  • Improved basic empty adjustment

Specifications

Output typePNP output (type ...FPKG...) or automatic NPN/PNP detection (type ...FAKG...)
Basic empty adjustment liquid levelContainer empty until liquid level is at least 20 mm below the sensor
Button press duration for basic empty adjustment2 to 6 seconds
LED indicationYellow LED off means switching output disabled; yellow LED on means switching output enabled

Frequently asked questions

How is basic empty adjustment performed?

Empty the container until the liquid level is at least 20 mm below the sensor, then press and hold the appropriate button for 2 to 6 seconds depending on the selected output state.

What does the yellow LED indicate?

The yellow LED being off means the switching output is disabled, and being on means the switching output is enabled.

Can the sensor be locked against accidental settings?

Yes, the device can be locked electrically to avoid accidental setting changes.

Does the sensor require maintenance?

The device operates without maintenance, but the sensing face and surrounding space should be kept free of deposits or foreign matter.