This manual describes the SIL certification of the OPTISWITCH 5300C vibrating level switch.
The document applies to point level sensors OPTISWITCH 5300C - Transistor (NPN/PNP) with SIL qualification, electronics module SG60HT-I, valid from HW Ver 1.0.0 and SW Ver 1.1.0. The versions "Plastic housing" and "external housing" are excluded.
It describes the safety function for level detection of liquids in safety-related systems according to IEC 61508, with up to SIL2 in single-channel architecture and up to SIL3 in multiple-channel architecture. It covers planning, safety-related characteristics, setup, diagnostics and servicing, proof tests and appendices for the test report and term definitions.
| Safety Integrity Level (single-channel) | SIL2 |
|---|---|
| Safety Integrity Level (multiple-channel) | SIL3 |
| Hardware error tolerance | HFT = 0 |
| Mode | Low demand mode, High demand mode |
| MTTR | 8 h |
| MTBF | 1.17 x 10^6 h (134 years) |
| Diagnostic test interval | < 120 s |
| Fault reaction time | < 2 s |
| PFDAVG (T1 = 1 year) | 0.026 x 10^-2 |
| PFH | 0.031 x 10^-6 1/h |
| MTTFd | 544 years |
| Performance Level | 3.12 x 10^-8 1/h (corresponds to "e") |
It supports up to SIL2 in single-channel architecture and up to SIL3 in a multiple-channel architecture.
Both transistor outputs must be evaluated, and screened cable must be used for connection.
The fault reaction time is less than 2 s.
The diagnostic test interval is less than 120 s.