Johnson Controls R-3712 Diode Restrictor Tee Product Bulletin

The R-3712 Diode Restrictor Tee is a low volume auxiliary device designed to regulate air flow direction. The .007 in. (.18 mm) restricted branch is identified with the symbol (⊗) above it. The R-3712 can function as a high signal selector, a signal override device, or a checkvalve (with the restricted branch capped).


Johnson Controls R-3712 Diode Restrictor Tee Product Bulletin - cover page
Brand
Johnson Controls
Category
Automation control Equipment
Document type
Product Leaflet
Language
English
Pages
2
File format
PDF
File size
70 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
3D745F4260C05EF5A9867007113FDA90

About this manual

The R-3712 Diode Restrictor Tee is a low-volume auxiliary device that regulates air flow direction. Its .007 in. (.18 mm) restricted branch is marked with a (⊗) symbol. It can serve as a high signal selector, a signal override device, or a checkvalve when the restricted branch is capped.

In high-selector use, the bulletin describes checkvalve and diode arrangements and notes that only high-volume thermostats can be used with more than two R-3712s, with one exhausting restrictor for each three diodes. In signal-override use, a 20 PSIG (140 kPa) signal can close a normally open valve or actuator on fan shutdown. Installation is in-line with 1/4 in. O.D. polytubing on barbed fittings.

What's inside

  • Restrictors
  • R-3712 Diode Restrictor Tee
  • Operation
  • Specifications
  • Installation
  • Application and Drawing Identification

Specifications

Restricted branch size.007 in. (.18 mm)
Mounting tubing1/4 in. O.D. polytubing
Signal override pressure20 PSIG (140 kPa)

Frequently asked questions

What is the R-3712 used for?

It is a low-volume auxiliary device designed to regulate air flow direction and can act as a high signal selector, signal override device, or checkvalve.

How is the R-3712 installed?

It is designed for in-line mounting using 1/4 in. O.D. polytubing connected to barbed fittings on the device.

What happens in a signal override application when the fan shuts down?

A 20 PSIG (140 kPa) signal overrides the control signal to close a normally open valve or actuator, and the R-3712 output rises to 20 PSIG.

How is the restricted branch identified?

It is identified by the symbol (⊗) above it.