DW15-630,DW15C-630 universal circuit breaker has rated current from 200A to 630A, AC 50Hz, rated working voltage to 1140V, and rated impulse withstand voltage 8kV. This circuit breaker is mainly used in distribution networks to distribute power, protect lines and power equipment from overload, undervoltage and short circuit. It can also be used in AC50Hz, AC400V power grid to protect motor overload, undervoltage and short circuit hazards. Under normal conditions, the circuit breaker can be used as line non-frequent switching and motor non-frequent switching.
The DW15-630 and DW15C-630 are universal circuit breakers with rated currents from 200 A to 630 A for AC 50 Hz distribution networks, with rated working voltage up to 1140 V. They are used to distribute power and protect lines, power equipment, and motors from overload, undervoltage, and short circuit.
The manual covers safety warnings, normal use and installation conditions, technical parameters, structure and working principle, outline and installation dimensions, weight, installation and operation, maintenance, fault analysis, warranty, and ordering notes. This manual is written in Chinese.
| Rated current | 200 A to 630 A |
|---|---|
| Rated frequency | 50 Hz |
| Rated working voltage | up to 1140 V |
| Rated impulse withstand voltage | 8 kV |
| Installation altitude | not more than 2000 m |
| Pollution degree | 3 |
| Net weight | DW15-630: 28.5 kg; DW15C-630: 47 kg |
| Auxiliary contact rated thermal current | 6 A |
| Auxiliary contact configuration | 3 normally open and 3 normally closed; 5 normally open and 5 normally closed on special order |
| Auxiliary contact rated control capacity | AC 300 VA; DC 60 W |
| Undervoltage release action time | delayed (1 to 2) ±0.5 s or instantaneous |
| Undervoltage release action voltage | (35% to 70%) Us trips; below 35% Us prevents closing; at or above 85% Us closes reliably |
| Shunt release power consumption | 418/494 VA (AC220/380 V); 432/285.3 W (DC110/220 V) |
| Closing electromagnet maximum instantaneous power | 5000/5300 VA (AC220/380 V); 3000 W (DC220 V) |
| Instantaneous overcurrent release (distribution use) | 10 In ±20%, non-adjustable |
| Instantaneous overcurrent release (motor protection use) | 12 In ±20%, non-adjustable |
| Long-time overcurrent release | 1.05 Ir does not trip within 2 h from cold state |
| Long-time inverse characteristic adjustment | Ir1 = (0.64 to 1.0) In |
| Thermal relay values | 3.2 A, 4 A, and 5 A correspond to 0.64 In, 0.8 In, and 1 In |
| Drawer positions | connected, test, and disconnected |
| Spacing between live parts | not less than 18 mm |
The rated current ranges from 200 A to 630 A.
The breaker is for AC 50 Hz with a rated working voltage up to 1140 V.
Ambient air temperature should be -5 to +40 C, with a 24-hour average not exceeding +35 C.
The DW15-630 weighs 28.5 kg and the DW15C-630 weighs 47 kg.