This manual introduces the installation, operation, maintenance and maintenance methods of MODAQO-M low-voltage intelligent distribution system.
Moeller MODAQO-M is a low-voltage intelligent distribution system that can be used as a distribution center, motor control center, or power and lighting control system. The manual covers receiving inspection, transport, storage, installation, cable connection, cleaning, commissioning, operation, maintenance, warranty, and service.
The system is intended for indoor installation in clean, dry, well-ventilated locations. It has passed national compulsory 3C certification and has a service life of more than thirty years. This manual is written in Chinese.
| Short-term maximum ambient temperature | +40 °C |
|---|---|
| 24-hour maximum average ambient temperature | +35 °C |
| Relative humidity at 40 °C | Not more than 50% |
| Altitude derating | Derating above 2000 m |
| Seismic intensity | Not higher than 8° |
| Minimum insulation resistance | 0.5 MΩ |
| Dielectric test voltage | 2000 V |
Check the delivery against the shipping list for completeness and inspect for transport damage; photograph any damage and report it promptly.
The minimum insulation resistance is 0.5 MΩ.
Electrical components must withstand 2000 V before entering the grid.
Newly commissioned equipment should be maintained after one year, then every two to five years depending on the environment.