This is an additional manual for a PLC connection manual that describes the connection information for the Shimaden Co., Ltd. SR253/SR90/SR80/MR13/FP93/SD16/EM70 Series models and is a supplement to the LT Editor and GP-PRO/PBIII for Windows Device/PLC Connection Manual.
This additional manual provides connection information for Shimaden Co., Ltd. SR253, SR90, SR80, MR13, FP93, SD16 and EM70 series controllers. It is described as a supplement to the LT Editor and GP-PRO/PBIII for Windows Device/PLC Connection Manual and as a provisional document whose information will be included in the next version of that manual.
The document describes system configuration for GP/GLC connections and includes cable diagrams for RS-232C, RS-422 2-wire and RS-422 4-wire connections, including 1:1 and 1:n configurations. It also gives cable length limits, termination resistance notes, installation steps for the shimaden.exe file, and EM70 Series communication settings such as baud rate, data length, stop bit and parity.
| RS-232C cable length | 15 meters or less |
|---|---|
| RS-422 (2-wire) cable length | 500 meters or less |
| RS-422 (4-wire) cable length | 600 meters or less |
| Maximum 1:1 connection | 31 units |
| EM70 Series baud rate | 19200 bps |
| EM70 Series data length | 7 bits |
| EM70 Series stop bit | 1 bit |
| EM70 Series parity | even |
The document lists LT Editor Ver.1.0 or later.
Double-click the “shimaden.exe” file on the CD-ROM and follow the setup program’s instructions.
Select [shimaden controller] for the “PLC Type” setting.
The EM70 Series baud rate is listed as 19200 bps.