Shimaden SR23 PID Controller User Manual

The Shimaden SR23 PID controller manual details installation, configuration, PID tuning, I/O, communication and safety specifications.


Shimaden SR23 PID Controller User Manual - cover page
Brand
Shimaden
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
13
File format
PDF
File size
779 KB
Published
01 October, 2026
Updated
01 October, 2026
Model
SR23
MD5 checksum
46D82F0BEB8A26E489DBEE35C65BEE37

About this manual

This manual describes the SR23 high‑resolution PID controller from Shimaden. It covers environmental limits, power requirements, input signal setup, PID parameter configuration, and output options for both contact and analog signals.

Additional sections explain event and alarm handling, communication interfaces (RS232C/RS485), and protection features such as IP66 front‑panel rating and digital lock functions. The document provides step‑by‑step procedures for system integration and troubleshooting. This manual is written in Chinese.

What's inside

  • Environmental Conditions
  • Electrical Specifications
  • Input Configuration
  • PID Parameter Settings
  • Output Configuration
  • Event and Alarm Settings
  • Communication Interface
  • Protection and Lock Settings
  • Installation and Quick Start

Specifications

Supply voltage100‑240 V AC ±10 % 50/60 Hz
Power consumption≤15 VA
Input noise (normal mode)≥40 dB min (50/60 Hz)
Safety standardsIEC 61010‑1, EN 61010‑1
IP protection ratingIP66 (NEMA 4X)
Dimensions (H×W×D)96 mm × 96 mm × 110 mm
Weight≤600 g
Output typesContact (Y) 240 V AC/2.5 A, Current 4‑20 mA DC, Voltage 0‑10 V DC

Frequently asked questions

What supply voltage does the SR23 accept?

The SR23 can be powered from 100 V to 240 V AC with a ±10 % tolerance at 50/60 Hz.

How many preset PID parameter groups are available?

The controller provides ten preset PID parameter groups.

What is the front‑panel protection rating?

The front panel is rated IP66 (equivalent to NEMA 4X).

Which communication interfaces are supported?

The SR23 offers optional RS232C and RS485 digital communication ports.

Download PDF (779 KB)

More Shimaden Manuals


View all Shimaden manuals →