Endress+Hauser RMx621/FML621 PROFINET Module Operation Manual

RMx621/FML621 PROFINET modules (PROFINET couplers) with version V3.03.01 and higher connect the RMx621/FML621 via a serial RS485 interface with an external module (HMS AnyBus communicator for PROFINET devices)


Endress+Hauser RMx621/FML621 PROFINET Module Operation Manual - cover page
Brand
Endress+Hauser
Category
Communications equipment
Document type
User Manual
Language
Chinese
Pages
29
File format
PDF
File size
6.1 MB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
48B90C157A83063FE8908C15CD248DC6

About this manual

Endress+Hauser RMx621/FML621 PROFINET Module Operation Manual describes connecting RMx621 or FML621 to PROFINET through an external PROFINET coupler over the serial RS485 interface. It covers installation, commissioning, process data, integration into a PROFINET network, configuration in TIA Portal 15.1, and technical data.

The manual includes requirements, connection and terminal diagrams, RS485 and process-value settings, device naming and status indications, payload structure, mapping of process data, and the coupler's physical and electrical specifications. This manual is written in Chinese.

What's inside

  • Overview
  • Installation
  • Commissioning
  • Process data
  • Integration into PROFINET network
  • Configuring the PROFINET coupler in TIA Portal 15.1
  • Technical data

Specifications

Dimensions120 mm x 75 mm x 27 mm (height, depth, width)
Supply voltage24 V DC +/-10%
Current consumptionTypical 100 mA, maximum 300 mA
RS485 interface38400 baud, 8 data bits, 1 stop bit, device address 01
Ambient temperature0 to 55 °C
Storage temperature-40 to +85 °C
Humidity0 to 95%, non-condensing
Protection ratingIP 20
Protective earth connectionThrough internal grounding of the DIN rail
CertificationUL - E203225, CE - 2004/108/EC, RoHS

Frequently asked questions

Which RMx621 and FML621 firmware versions support the PROFINET option?

The PROFINET option applies to RMx621 V3.09.00 and higher and FML621 V1.03.00 and higher.

What is the maximum number of process values that can be output?

The maximum number of process values is limited to 48.

What RS485 settings are required on RMx621/FML621?

Set the unit address to 1 and the baud rate to 38400.

Can a PROFINET coupler purchased from HMS be used as a replacement?

No, only preconfigured PROFINET couplers purchased through Endress+Hauser can be used as replacement devices.