RMx621/FML621 PROFINET modules (PROFINET couplers) with version V3.03.01 and higher connect the RMx621/FML621 via a serial RS485 interface with an external module (HMS AnyBus communicator for PROFINET devices)
Endress+Hauser RMx621/FML621 PROFINET Module Operation Manual describes connecting RMx621 or FML621 to PROFINET through an external PROFINET coupler over the serial RS485 interface. It covers installation, commissioning, process data, integration into a PROFINET network, configuration in TIA Portal 15.1, and technical data.
The manual includes requirements, connection and terminal diagrams, RS485 and process-value settings, device naming and status indications, payload structure, mapping of process data, and the coupler's physical and electrical specifications. This manual is written in Chinese.
| Dimensions | 120 mm x 75 mm x 27 mm (height, depth, width) |
|---|---|
| Supply voltage | 24 V DC +/-10% |
| Current consumption | Typical 100 mA, maximum 300 mA |
| RS485 interface | 38400 baud, 8 data bits, 1 stop bit, device address 01 |
| Ambient temperature | 0 to 55 °C |
| Storage temperature | -40 to +85 °C |
| Humidity | 0 to 95%, non-condensing |
| Protection rating | IP 20 |
| Protective earth connection | Through internal grounding of the DIN rail |
| Certification | UL - E203225, CE - 2004/108/EC, RoHS |
The PROFINET option applies to RMx621 V3.09.00 and higher and FML621 V1.03.00 and higher.
The maximum number of process values is limited to 48.
Set the unit address to 1 and the baud rate to 38400.
No, only preconfigured PROFINET couplers purchased through Endress+Hauser can be used as replacement devices.