This document is the instruction manual of FS-2000E flame sensor. It introduces the function and features of the sensor, such as the ability to detect ultraviolet rays in the flames and issue an alarm, as well as the C (N/C, N/O) output to meet professional applications. In addition, the memory LED enables you to find the initiated sensor out of a series of sensors. Area adjustment mechanism brings wide selection of protection angle. Quick separation of sensor and base eases installation and maintenance.
The TAKEX FS-2000E is a flame sensor designed to detect ultraviolet rays contained in flames and to initiate an alarm. This instruction manual covers parts description, installation, wiring, and operation of the sensor for professional applications; it is not a fire-preventing device.
The unit provides form C (N/C, N/O) output, a memory LED to identify the initiated sensor, and an area adjustment mechanism for a wide selection of protection angles. The sensor unit separates quickly from the base for easier installation and maintenance, and detection sensitivity and timer can be set using the mode selector.
| Operating voltage | 10 to 30VDC (non-polarity) |
|---|---|
| Standby current | 25mA |
| Alarm current (buzzer ON) | 75mA Max. |
| Alarm current (buzzer OFF) | 40mA Max. |
| Detection timer settings | 0.2 sec, 1 sec, 6 sec, 30 sec |
| Alarm output action | Offdelay (detection time + 2 sec.) |
| Alarm output capacity | 0.3A or less (protective resistance 3.3 ohms) |
| Memory LED duration | Blinks for 3 min, then lights on for 47 min |
It detects ultraviolet rays contained in flames and initiates an alarm; it does not detect smoke or heat.
Alarm output stops 2 seconds after the flame goes out, and alarm sound and LED stop 10 seconds later.
Yes, the buzzer can be turned off by mode selector No.1 when external output is used.
Yes, the sensor is for indoor use only and should not be installed in direct sunlight or rain.