LAPP 679 VFD Cable Selection Guide

This document provides a cable selection guide, which includes an AWG size selection table and a voltage drop factor table.


LAPP 679 VFD Cable Selection Guide - cover page
Brand
Lapp
Category
Other Electronics
Document type
Product Leaflet
Language
English
Pages
1
File format
PDF
File size
430 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
183CD287F4EEB1250A372194818A9D63

About this manual

This document provides technical data for selecting LAPP 679 VFD cables. It includes motor properties tables that suggest wire AWG sizes based on drive horsepower (HP) and voltage (230V, 460V, 575V) according to NEC allowable conductor ampacity and regulatory codes.

The guide also lists voltage drop factors for various drive HPs and voltages to assist in calculating voltage drop over specific distances. It references NEC Article 430-122 for full load current calculations and Article 310.15 for ampacity, noting that 60°C column ampacities are referenced to avoid safety hazards.

What's inside

  • Motor Properties
  • AWG Size Selection Chart
  • Voltage Drop Factor
  • NEC Allowable Conductor Ampacity
  • Full Load Current
  • Drive HP
  • Voltage
  • Ampacity
  • Safety Considerations
  • LAPP MOTOR EXAMPLE

Specifications

Document Number800-774-3539
Product Series679
Supported Voltages230V 3ø, 460V 3ø, 575V 3ø
Reference StandardNEC Article 430-122
Temperature Rating Reference60°C column

Frequently asked questions

How is the required AWG wire size calculated per NEC?

Multiply the full load current (FLC) by 125% to determine the required ampacity for the wire size.

What temperature column is used for ampacity references?

The 60°C column ampacities are referenced to avoid safety hazards.

How do you calculate voltage drop over a distance?

Multiply the distance to the motor by the specific voltage drop factor found in the table.

Download PDF (430 KB)