This file is an instruction manual for PKK-111 and PKS-111 current sensors. It introduces the application scenarios, technical parameters, appearance structure and other information of the sensors.
This instruction manual covers the HiTECH PKK-111 and PKS-111 current detecting switches. The PKK-111 is a DIN-rail mounted unit (EN 50 0222) and the PKS-111 uses an 11-pin plug-and-socket circular connector (IEC 67-1-18a). The devices convert a current applied to the "Iin" terminals into a relay output and can work as a limit switch, a window switch or a differential switch, for alarm switching, current range indication and empty/fill-type control.
The manual gives the technical data, describes the input range selector, the A and B operation mode selectors, the C relay mode selector and the IA/IB switching level potentiometers, and explains the L1 and L2 LEDs. It also covers dimensions, step-by-step calibration for each operating mode, maintenance and repair, storage conditions and the HiTECH performance guarantee.
| Supply voltage | 230, 110, 24 V AC; 50 to 60 Hz or 24 V DC; -15 to 10% |
|---|---|
| Current input | 0/5 mA or 0/20 mA, selectable |
| Adjustable range | 0 to 6 mA or 0 to 26 mA |
| Consumption | 2.5 VA |
| Input impedance | 132Ω (0/5 mA); 57Ω (0/20 mA) |
| Overload capacity | max. 100 mA; continuous overload |
| Relay output | SPTD; 250 V AC; 5 A |
| Ambient temperature | -10 to 55°C |
| Enclosure | IP 40 |
| Switching delay | approx. 1 sec |
| Weight | 0.21 kg |
The input is selectable between 0/5 mA and 0/20 mA, with an adjustable range of 0 to 6 mA or 0 to 26 mA.
It can operate in limit switch, window switch or differential switch mode, selected with the A and B DIP-switches.
The PKK-111 mounts on DIN 46277/3 rail, while the PKS-111 mounts on an 11-pin plug-and-socket type circular connector.
Store the device at an environment temperature of -25 to +60 °C (-13 to +140 °F).