HiTECH PKK-111 PKS-111 Current Detecting Switch Instruction Manual

This file is an instruction manual for PKK-111 and PKS-111 current sensors. It introduces the application scenarios, technical parameters, appearance structure and other information of the sensors.


HiTECH PKK-111 PKS-111 Current Detecting Switch Instruction Manual - cover page
Brand
Hi-Tech
Category
Current Monitor
Document type
User Manual
Language
English
Pages
4
File format
PDF
File size
130 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
3C51CD49937195A8F9A899DE5F8F318D

About this manual

This instruction manual covers the HiTECH PKK-111 and PKS-111 current detecting switches. The PKK-111 is a DIN-rail mounted unit (EN 50 0222) and the PKS-111 uses an 11-pin plug-and-socket circular connector (IEC 67-1-18a). The devices convert a current applied to the "Iin" terminals into a relay output and can work as a limit switch, a window switch or a differential switch, for alarm switching, current range indication and empty/fill-type control.

The manual gives the technical data, describes the input range selector, the A and B operation mode selectors, the C relay mode selector and the IA/IB switching level potentiometers, and explains the L1 and L2 LEDs. It also covers dimensions, step-by-step calibration for each operating mode, maintenance and repair, storage conditions and the HiTECH performance guarantee.

What's inside

  • Applications
  • Technical Data
  • Accessories
  • Operation
  • Dimensions
  • Calibration
  • Maintenance, Repair
  • Storage Conditions
  • Performance Guarantee

Specifications

Supply voltage230, 110, 24 V AC; 50 to 60 Hz or 24 V DC; -15 to 10%
Current input0/5 mA or 0/20 mA, selectable
Adjustable range0 to 6 mA or 0 to 26 mA
Consumption2.5 VA
Input impedance132Ω (0/5 mA); 57Ω (0/20 mA)
Overload capacitymax. 100 mA; continuous overload
Relay outputSPTD; 250 V AC; 5 A
Ambient temperature-10 to 55°C
EnclosureIP 40
Switching delayapprox. 1 sec
Weight0.21 kg

Frequently asked questions

What current input ranges does the current detecting switch support?

The input is selectable between 0/5 mA and 0/20 mA, with an adjustable range of 0 to 6 mA or 0 to 26 mA.

Which operating modes can the device be set to?

It can operate in limit switch, window switch or differential switch mode, selected with the A and B DIP-switches.

How are the PKK-111 and PKS-111 mounted?

The PKK-111 mounts on DIN 46277/3 rail, while the PKS-111 mounts on an 11-pin plug-and-socket type circular connector.

What are the storage conditions?

Store the device at an environment temperature of -25 to +60 °C (-13 to +140 °F).