Georg Fischer Signet 2610 Process Optical Dissolved Oxygen Sensor Communication Protocol Manual

This document is about Signet 2610 process optical dissolved oxygen sensor communication protocol manual, which introduces how to connect the sensor to a controller or recorder via RS485 Modbus.


Georg Fischer Signet 2610 Process Optical Dissolved Oxygen Sensor Communication Protocol Manual - cover page
Brand
Georg Fischer
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
1.1 MB
Published
20 October, 2023
Updated
20 October, 2023
MD5 checksum
D1C769D71DC8396DAE9DB868811B929A

About this manual

This document serves as a communication protocol manual for the Signet 2610 Process Optical Dissolved Oxygen Sensor. It details how the sensor connects to controllers or recorders via RS485 Modbus, including power connection instructions and default settings for analog outputs.

The manual provides comprehensive tables for communication protocol registers and calibration registers. It defines specific register addresses for reading and writing data such as dissolved oxygen concentration, temperature, salinity, and atmospheric pressure. Additionally, it outlines a step-by-step procedure for calibrating the sensor using 100% and 0% saturation environments. This manual is written in Chinese.

What's inside

  • Power Connection
  • Communication Protocol Registers
  • Calibration Registers
  • Real-time Salinity and Pressure
  • Calibration Procedure
  • Calibration Calculation

Specifications

Connection InterfaceRS485 Modbus
Default Device Address1
Default Communication Baud Rate19200
Data Quality ID Default0x0030 (48)
Default Atmospheric Pressure1013.25 mbar

Frequently asked questions

What is the default unit for dissolved oxygen concentration?

The default unit for dissolved oxygen concentration is mg/L.

What is the valid range for real-time salinity values?

Real-time salinity values must be written in PSU units ranging from 0 to 42 PSU.

What is the valid range for real-time atmospheric pressure?

Real-time atmospheric pressure values must be written in millibar, ranging from 506.625 to 1114.675 mbar.

Is regular calibration required for this sensor?

No, regular calibration is not required as the sensor cap is factory calibrated to 2% accuracy.