KUTAI ECU-04 Generator Auto Start Control Unit User Manual

The ECU-04 is a manual generator auto start control for auto start generator. The device uses standard two-wire signals from any Automatic Transfer Switch or any standard remote mounted ON / OFF switch to automatically initiate the generator's starting cycle. In case of generator starting failures, this device has maximum of 3 attempts of preheat and start with adjustable time from1 to 25 seconds interval. This module is composed of microprocessors to minimized dimension. Encapsulated in factory designed chassis to protect them from vibration and moisture.


KUTAI ECU-04 Generator Auto Start Control Unit User Manual - cover page
Brand
KUTAI
Category
Generator
Document type
User Manual
Language
English
Pages
4
File format
PDF
File size
457 KB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
A21F422621F3EA02E4CF73794A1056E2

About this manual

The KUTAI ECU-04 Generator Auto Start Control is a microprocessor-based module designed to convert manual key-start generators into automatic-start units. It mimics the action of turning a panel key and starting the generator manually using standard two-wire signals from an Automatic Transfer Switch or a remote ON/OFF switch. The device features a compact epoxy-encapsulated chassis to protect against vibration and moisture.

What's inside

  • Introduction
  • Standard Features
  • Specifications
  • Electrical Connections
  • Time Delay Setting
  • Alarm Indicators
  • Connection Details
  • Typical Wiring Diagram

Specifications

DC Supply Voltage12 Vdc (ECU-05-12V)
24V DC Supply Voltage24 Vdc (ECU-05-24V)
Max. Input Voltage (12V model)18 Vdc
Max. Input Voltage (24V model)36 Vdc
Alternator Input Voltage Range100 - 240 Vac (+/- 10%)
Alternator Input Frequency Range50 - 60 Hz
Static Power ConsumptionLess than 0.03 watts
Starter switch Signal Output30Amp @ 12/24 Vdc
Operating Temperature-20 to +60 ˚C
Dimensions162.0 (L) x 112.0 (W) x 31.0 (H) mm

Frequently asked questions

How many start attempts does the ECU-04 make in case of failure?

The device has a maximum of 3 attempts of preheat and start.

What is the recommended pre-heat time setting?

The recommended pre-heat time is 5 seconds.

What is the recommended start-up time setting?

The recommended start-up time is 4 to 8 seconds.

What does the SW switch control?

SW is ON for Diesel Engines with Pre-Heat and OFF for Gasline Engines with Carburetor.