KUTAI EG3002F Electronic Engine Governor Controller User Manual

This document is the user manual of the EG3002F electronic engine governor controller produced by KUTAI Electronics


KUTAI EG3002F Electronic Engine Governor Controller User Manual - cover page
Brand
KUTAI
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
8
File format
PDF
File size
3.5 MB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
6059B29A1E7E7B5CE326DEA9252F3D93

About this manual

The KUTAI EG3002F is an electronic controller designed to take a signal from a magnetic pickup and compare it with a preset engine speed to control drive voltage to the actuator. It features engine start smoke suppression, idle speed control, and adjustable ramp time. The unit is applicable for MPU frequency ranges of 600 to 9500 Hz and supports settings for Cummins high-gain (PT Pump) engines and extreme slow response engines.

What's inside

  • Summary
  • Specification
  • Appearance / Dimensions / Installation Drawing
  • Potentiometer Adjustments and DIP Switch Functions
  • Wiring Connections
  • Adjustment
  • Trial Run
  • Speed Gain, INT, and DIF Setting
  • Remote Speed Pot Adjustment
  • Parallel Generator Operation

Specifications

Speed variationless than +/- 0.25%
Current Continuous7A min. 0.5A Max. 15A 10 seconds
MPU Signal Frequency10 – 10,000 Hz
Operating Temperature-40 to +80 ˚C
Dimensions147.0 (L) x 114.0 (W) x 50.0 (H) mm

Frequently asked questions

What is the applicable MPU frequency range?

The unit is applicable for MPU frequency range of 600 to 9500 Hz.

Does the controller support Cummins PT Pump engines?

Yes, the unit has settings for use with Cummins high-gain (PT Pump) engines.

What is the recommended speed droop for parallel generator operation?

A speed Droop of 2% at maximum load is recommended.