This document is the user guide for Kutai CH3612 and CH3624 automatic battery chargers. It describes the product's specifications and features, including input protection, output environment, vibration, charge mode, mounting type, efficiency, low battery voltage alarm output, capacity and weight.
This user guide explains how to install and operate the Kutai CH3612 and CH3624 automatic battery chargers. It details specifications such as voltage, current, and environmental ratings. The guide also covers low-voltage alarm settings, display indicators, and safety precautions including proper cable sizing and ventilation. Mounting options include panel mount or DIN rail, with optional DIN rail kits available separately.
| Power Input | 100 − 277 Vac |
|---|---|
| Frequency | 47 − 63 Hz |
| DC Output (CH3612) | 13.8 Vdc / 6A Max. |
| DC Output (CH3624) | 27.6 Vdc / 3A Max. |
| Operation Temperature | -20 − +60 ˚C |
| Storage Temperature | -30 − +80 ˚C |
| Relative Humidity | Max. 90% |
| Low Battery Voltage Alarm (CH3612) | Less than 10 Vdc |
| Low Battery Voltage Alarm (CH3624) | Less than 20 Vdc |
| Suitable Battery Type | Gel, Flooded Lead Acid & AGM |
The minimum battery voltage for CH3612 must be higher than 6 Vdc, otherwise the charger will shut down.
The minimum battery voltage for CH3624 must be higher than 12 Vdc, otherwise the charger will shut down.
The output voltage for CH3612 is 13.8 Vdc +/- 1%.
The output voltage for CH3624 is 27.6 Vdc +/- 1%.