The KUTAI EC-05 Auto Start Module is designed to automatically start and stop gasoline engine generators based on signals from a remote switch or an Automatic Transfer Switch (ATS). It is specifically suitable for key-start generators equipped with a starter motor but lacking an automatic start and stop function. The module includes a choke control function, making it particularly effective for use in cold regions. This manual is written in Chinese.

What's inside

  • Specification
  • Product Overview
  • External Wiring
  • Time Delay and Function Settings
  • LED Status Indicators
  • Appearance and Dimensions
  • Recommended Connections

Specifications

Fuse Specification5 x 20mm S505-10A slow-blow
Operating Temperature-20 to +70 ˚C
AC Power Input Voltage5 - 300 V ac single-phase
AC Power Input Frequency50 / 60 Hz
Stop Signal Output7 Amps @ 12 / 24 Vdc
Weight170 g +/- 2%

Frequently asked questions

Can the EC-05 be used in cold regions?

Yes, the module has a choke control function making it especially suitable for use in cold regions.

What is the setting range for the stop timer?

The stop action timer setting range is 1 to 20 seconds with stepless adjustment.

How many times will the engine attempt to start automatically?

The engine will attempt to start 3 times if it fails to start normally.