KUTAI EA440 Generator Automatic Voltage Regulator Operation Manual

This manual introduces the use of the EA440 self-excited automatic voltage regulator.


KUTAI EA440 Generator Automatic Voltage Regulator Operation Manual - cover page
Brand
KUTAI
Category
Generator
Document type
User Manual
Language
Chinese
Pages
5
File format
PDF
File size
477 KB
Published
19 October, 2023
Updated
19 October, 2023
Model
EA440
MD5 checksum
06324D9AFC44CF23220641CBFC9EAC2E

About this manual

This manual provides operational instructions for the KUTAI EA440 automatic voltage regulator, designed for use with Newage SX440 generators. It details electrical specifications, wiring diagrams, voltage and stability adjustments, droop settings, and field flashing procedures. The document also covers parallel operation with current transformers and troubleshooting common issues like voltage failure or instability. Safety warnings are included regarding improper field flashing and wiring errors. This manual is written in Chinese.

What's inside

  • Specification
  • Wiring
  • Adjustment
  • Field Flashing
  • Parallel Function
  • Troubleshooting

Specifications

Input Voltage190 – 264 Vac, 1 phase 2 wire
Frequency50 / 60 Hz, selectable
Output VoltageMax. 90 Vdc @ power input 207 Vac
Voltage RegulationLess than +/- 1% (with 4% engine governing)
Operating Temperature-40 to +70 ˚C
Dimensions150.0 (L) x 135.0 (W) x 48.0 (H) mm
Weight418 g +/- 2%

Frequently asked questions

How do I adjust the generator output voltage?

Adjust the volt VR on the AVR board or use an external 1K ohm trimmer. Turn the trimmer clockwise until the rated voltage is reached.

What should I do if the generator fails to build voltage?

Check for reversed field polarity or insufficient residual voltage. If polarity is reversed, swap F+ and F-. If residual voltage is below 5 Vac, flash the field for 3 seconds using a 3–5 ohm resistor for full wave or 5–10 ohm for half wave AVR.

How do I set up the AVR for parallel operation?

Connect a 10VA current transformer (CT) to the generator line not supplying sensing to the regulator. Ensure the CT signal phase relationship is correct with the regulator sensing voltage.