Kutai EA350 Self-Excited Automatic Voltage Regulator Operation Manual

Kutai EA350 is a self-excited automatic voltage regulator for general generators, compatible with Marathon SE350.


Kutai EA350 Self-Excited Automatic Voltage Regulator Operation Manual - cover page
Brand
KUTAI
Category
Other Electronics
Document type
User Manual
Language
English
Pages
6
File format
PDF
File size
394 KB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
551CFF7DEB38678D1D5027394BDA887F

About this manual

This document provides the operation manual for the Kutai EA350 Self-Excited Automatic Voltage Regulator. It is designed for use with general generators, specifically noting compatibility with the Marathon SE350 for reference purposes only. The device is certified to EN61204-3 : 2001 standards.

What's inside

  • Specification
  • Wiring
  • Voltage Adjustment
  • Stability Adjustment
  • V/Hz Roll-Off Frequency Selection
  • Corner Frequency Jumper
  • Voltage Adjust Rheostat Jumper
  • Stability Selection
  • Operational Test
  • System Start-Up

Specifications

Input Voltage85 ~ 135 VAC / 190 ~ 240 VAC
Frequency50 / 60 Hz, Jumper selectable
Output Voltage (Max)36 VDC @ 120 VAC input
Output Voltage (Max)73 VDC @ 240 VAC input
Continuous Current4A
Intermittent Current7A for 10 sec
Resistance Range15 ohm to 100 ohm
Voltage Regulation< ± 1%
Operating Temperature- 40°C ~ 60°C
Burden250 / 500VA Max.
Power DissipationMax. 8 watt
Dimensions99.5mm L * 67mm W * 47.5mm H
Weight205g ± 2%

Frequently asked questions

What is the minimum exciter field dc resistance required?

The exciter field dc resistance must be 15 ohms or greater and less than 100 ohms.

How do you adjust the generator output voltage?

Use the screwdriver adjustable potentiometer; turning it clockwise increases the generator output voltage.

What is the residual voltage requirement for operation?

The residual voltage at the AVR terminal must be greater than 5 VAC.

What type of voltmeter should be used for voltage readings?

All AC voltage readings must be taken with an average reading voltmeter.