PR 7501V104-UK Field Mounted HART Temperature Transmitter User Manual

The product is a HART temperature transmitter that provides multiple interfaces and supports multiple protocols, with automatic self-calibration and fault detection


PR 7501V104-UK Field Mounted HART Temperature Transmitter User Manual - cover page
Brand
PR
Document type
User Manual
Language
Chinese
Pages
67
File format
PDF
File size
4.1 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
95CD0E1C02F1E44B4C668E2A4A3C91B9

About this manual

This is the user manual for the PR 7501V104-UK field-mounted HART temperature transmitter. It provides detailed instructions for installation, calibration, HART communication, and device operation. The device supports RTD, TC, and mV inputs with 4–20 mA analog output and HART 7 functionality. It is designed for hazardous areas and includes a local operator interface with optical buttons. Technical specifications include operating temperature ranges, accuracy, and EMC immunity.

The manual also covers accessories, mounting, wiring, display settings, and programming via the local interface or HART. It includes installation drawings for various certification standards and lists approvals such as ATEX, IECEx, and FM. The device supports multiple languages and has configurable backlight and error indication colors. This manual is written in Chinese.

What's inside

  • Warning
  • Applications
  • Order
  • Accessories
  • Technical Data
  • Block Diagram
  • Marking
  • Protection Degree
  • Assembly and Disassembly
  • Connections

Specifications

Input SignalsTC, RTD, Ohm, bipolar mV
Output4...20 mA analog PV output and HART
Display Resolution96 x 64 pixels
Operating Temperature (Silicone O-ring)-40°C to +85°C
Operating Temperature (FKM O-ring)-20°C to +85°C
Supply Voltage (Ex ia)10...30 VDC
HART Protocol RevisionsHART 7 and HART 5
Accuracy (TC B1)> 400°C
Accuracy (TC B4)< 85°C
Protection DegreeIP54 / IP66 / IP68 / type 4X
DimensionsØ 110 mm
Weight1.3 kg
Wire Size0.13...1.5 mm² / AWG 26...16 stranded wire
Isolation Voltage1.5 kVAC / 50 VAC
Signal/Noise Ratio> 60 dB
Response Time (Programmable)1...60 s
Long Term Stability0.1% of span / year
Sensor CurrentNom. 0.2 mA
Max. Offset on Input Signal50% of selected max. value
Load Resistance≤ (Vsupply - 10) / 0.023 [Ω] with backlight
HART Start-up TimeMax. 5 s
EMC ImmunityNAMUR NE 21, A criterion, burst … < ±1% of span
CertificationsATEX, IECEx, FM, CSA, INMETRO, EAC

Frequently asked questions

What are the input types supported by the 7501V104-UK?

It supports RTD, TC, Ohm, and bipolar mV inputs.

What is the operating temperature range with a silicone O-ring?

It is -40°C to +85°C.

What HART protocol revisions are supported?

It supports HART 7 and HART 5.

What is the long-term stability of the device?

It is 0.1% of span per year.

Download PDF (4.1 MB)

More PR Manuals


View all PR manuals →