This manual contains safety and operating instructions for the neutral grounding resistor.
This manual provides safety and installation instructions for Vishay’s Neutral Grounding Resistors. It covers compliance with manual instructions and installation procedures, shipping and receiving guidelines, enclosure and resistor bank descriptions, site installation requirements, commissioning tests, and operational safety procedures. The document also includes maintenance and replacement parts information.
The manual emphasizes safety precautions, proper handling during shipping and storage, correct mounting and ventilation clearances, and detailed steps for commissioning and operation. It includes technical specifications for resistance and insulation tests, and guidelines for personnel safety during maintenance and testing.
| Resistance Test | Must be the value stamped on the nametag + 10 % unless specified otherwise |
|---|---|
| Insulation Test | Insulation resistance > 100 MΩ |
| Maximum Applied Voltage for AC High-Potential Test | (2.25 x phase voltage) + 2000 V at 60 Hz |
The resistance value must match the value stamped on the nametag plus 10%, unless otherwise specified.
The insulation resistance between the resistor elements and the enclosure must be greater than 100 MΩ.
The maximum applied voltage is (2.25 x phase voltage) + 2000 V at 60 Hz.