The manual is an instruction manual for the LE4SA timer, which introduces the function setting mode, output operation mode, specifications, time setting, connection, safety considerations, etc. of the timer.
The document serves as a user guide for the Autonics LE4SA timer. It details front panel identification, including displays for time progression, settings, operation modes, and output status. The manual explains various function setting modes such as One-Shot and Time Range, along with different output operation modes like ON Delay, Instantaneous Contact, and Time Limit contacts.
| Power supply | 24-240VAC~ 50/60Hz, 24-240VDC= |
|---|---|
| Display method | LCD Display(BacHight) |
| Allowable voltage range | 90 ~ 110% of rated voltage |
| Power consumption (AC) | Max. 4VA |
| Power consumption (DC) | Max. 1.6 |
| Contact capacity | 250VAC~ 3A resistive load |
| Ambient temperature | 10 ~ 55 O(at non-treezing status) |
| Storage temperature | 25 ~ 65°C at non-treezing status) |
The One-Shot output time setting range is from 0.01 sec to 99.99 sec.
The minimum setting time is 0.01 sec, though it can be set to 0 since no min. setting time is applied in these modes.