This document serves as a design-in guide for the Philips Surge Protection Device 277V (SPD), intended for integration into Class I and Class II outdoor luminaires. It explains how the device protects lighting installations from damaging voltage spikes, including those caused by lightning strikes, by limiting differential and common mode surge voltages.
| Protection Level (Differential Mode) | 1.6 kV between L and N |
|---|---|
| Protection Level (Common Mode) | 2.5 kV |
| Nominal Current | up to 5kA |
| Single Strike Capability | 5 to 10kA |
| Wire Cross Section | 0.5 - 4 mm2 |
| Mounting Screw Type | M8 |
| Product Length | 89 mm |
| Product Width | 41 mm |
| Product Height | 38 mm |
It is a Type 3 product characterized by a combination of voltage waves (1.2/50 μs) and current waves (8/20 μs).
Yes, it can be used in combination with electronic drivers and different lamp types such as LEDs, HID, and fluorescent lamps.
It is important to mount the device with the connection terminals facing downward.