This manual describes the operation of F series humidity and humidity-temperature transmitters, including power supply, output range, temperature operating range and temperature limits, humidity limits, temperature compensation, sensor protection, output signals, wiring diagrams, grounding, installation, cleaning or replacing the dust filter (through wall model), periodic calibration check and other contents.
The ROTRONIC F Series transmitters are designed to measure relative humidity or a combination of humidity and temperature in commercial HVAC installations, clean rooms, research laboratories, and light manufacturing areas. These devices utilize the durable ROTRONIC HYGROMER capacitive sensor and feature electronic compensation for accurate measurements across varying temperatures.
The manual covers various installation methods including space mount (surface) and duct mount (through wall) configurations. It details power supply requirements for both 2-wire loop powered and 3-wire models, output signal specifications (current or voltage), wiring diagrams, grounding recommendations, and maintenance procedures such as cleaning dust filters.
| Humidity Output Range | 0 to 100%RH |
|---|---|
| Temperature Operating Range (Electronics) | -5 to 50°C |
| Supply Voltage (2-Wire Loop Powered) | 10..35 VDC |
| Supply Voltage (3-Wire) | 10..35 VDC or 24 VAC |
| Temperature Sensor Type (Humidity+Temp models) | RTD Pt100 |
The F series features the ROTRONIC HYGROMER capacitive humidity sensor.
3-Wire transmitters offer 0-20 mA, 4-20 mA, 0-1 V, or 0-5 V outputs.
Through wall models are supplied with a standard dust filter to protect the sensors.
Operation does not require grounding, but it is recommended especially in low humidity environments.