DVR DVR2000E+ Digital Voltage Regulator Installation and Operation Manual

The DVR®2000E+ digital voltage regulator is an electronic solid-state microprocessor-based controller that controls the output voltage of an AC brushless generator by adjusting the current entering the excitation machine's magnetic field. The regulator has multiple control modes, features, and protection functions.


DVR DVR2000E+ Digital Voltage Regulator Installation and Operation Manual - cover page
Brand
DVR
Document type
User Manual
Language
Chinese
Pages
42
File format
PDF
File size
1.5 MB
Published
10 December, 2022
Updated
28 September, 2023
MD5 checksum
CE70293A8A573126E7D2BFC5796A64ED

About this manual

The DVR2000E+ is a microprocessor-based automatic voltage regulator (AVR) designed to control the output voltage of brushless AC generators. It utilizes input power from a single-phase permanent magnet generator (PMG) and features a fully sealed installation structure with an integrated human-machine interface (HMI). The device supports various control modes, including Single-Phase AVR, Three-Phase AVR, and Field Current Regulation (FCR), allowing for precise voltage adjustment and system stability. This manual is written in Chinese.

What's inside

  • Overview
  • Features and Protections
  • Specifications
  • Installation
  • Human-Machine Interface (HMI)
  • Graphical User Interface
  • Maintenance and Troubleshooting

Specifications

Operating Power Supply Voltage180-240VAC
Operating Frequency250-300Hz
Power Rating350VA
Generator Voltage Detection Range100-630VAC
Field Current Continuous Rating75Vdc, 3.0Adc
Voltage Regulation Accuracy (AVR Mode)±0.25%
Operating Temperature Range-40°C ~ +70°C
Weight3.1 lbs (1361g)

Frequently asked questions

What control modes does the DVR2000E+ support?

It supports Single-Phase AVR, Three-Phase AVR, and Manual/Field Current Regulation (FCR) modes.

What is the voltage adjustment accuracy in AVR mode?

The voltage regulation accuracy is ±0.25% at constant power factor and frequency.

How does the device handle soft start?

It features a configurable soft-start control with an adjustable time range of 2 to 120 seconds.