About this manual

This document serves as a quick reference manual for the Inovance IVC2L series Programmable Logic Controller (PLC) main module. It is designed to assist users in the design, installation, connection, and maintenance of the product by providing rapid access to essential information. The manual includes details on hardware specifications, features, usage methods, and a list of optional accessories. This manual is written in Chinese.

What's inside

  • Introduction
  • Model Description
  • Terminal Definitions
  • Power Specifications
  • Input Characteristics
  • Output Specifications
  • Interrupt Input Connection

Specifications

Input Voltage Range85-264 Vac
Rated Output Current (5V/GND)1000 mA
Rated Output Current (24V/GND)650 mA
Maximum Output Power35W
High Speed Input Frequency (X0, X1)50kHz
High Speed Input Frequency (X2-X5)10kHz
Relay Output Max Current (Resistive)2A/1 point
Transistor Output Max Current (Resistive)0.3A/1 point

Frequently asked questions

What is the function of the COM terminal?

The COM terminal is the common ground for both the +24Vdc auxiliary power supply and input signals.

How do relay and transistor outputs differ?

Relay outputs are dry contacts suitable for high voltage/current loads, while transistor outputs are for high-frequency applications like servos.