This Technical Note provides information about a problem with the RFI filter B84143-A600-S9 (10025451) and the corrective actions required to avoid personal injury.
This technical note from ABB Oy describes an RFI filter (B84143-A600-S9) used at the input of SAMI STAR and ACS 600 frequency converters to limit conducted emissions. It warns of potential capacitor deformation and explosion risks during installations between 1996-2000, requiring immediate removal if deformed.
The document provides corrective actions including visual inspection procedures and replacement with a new Epcos RFI filter, emphasizing that replacement requires mechanical engineering verification and compliance with new filter specifications.
| Filter type | RFI filter |
|---|---|
| Filter components | chokes and capacitors |
| Capacitor connections | between the phases and virtual star point and also between star point and ground |
| Affected models | SAMI STAR 200F380 - 400F380, SAMI STAR 250F500 - 500F500, SAMI STAR 200F690 - 630F690, ACS607-0210-3 - ACS607-0610-6 |
The RFI filter is used at the input of SAMI STAR and ACS 600 frequency converters to fulfill requirements to limit conducted emissions.
A defective filter capacitor can cause deformation to the RFI filter and may lead to explosion without safety vents, potentially causing personal injuries.
Remove the RFI filter immediately and run the system without it as a temporary solution.