The 8DJ20 switchgear is a factory-assembled, type-tested, metal-enclosed switchgear for indoor installation, used for power distribution in substations. It is suitable for industrial environments, damp, sandy or dusty areas, and some special outdoor substations. It has a highly compact design and can be used in compact substations, wind power stations, etc.
This catalog details the Siemens 8DJ20 gas-insulated switchgear, designed for indoor installation and suitable for harsh environments. It includes configurations for radial transformer panels, ring-main feeders, and transformer feeders with HV HRC fuse assemblies. The switchgear is maintenance-free, climate-independent, and features a hermetically sealed primary enclosure with SF6 insulation. Available in three overall heights (1200 mm, 1400 mm, 1760 mm), it supports compact substations and switchgear rooms with control aisles.
Technical specifications cover electrical data, filling pressure, temperature ratings, and withstand voltages. Options include motor operating mechanisms, surge arresters, and auxiliary switches. The product complies with IEC standards and is certified under ISO 9001 and ISO 14001.
| Rated Voltage | 7.2 kV, 12 kV, 15 kV, 17.5 kV, 24 kV |
|---|---|
| Rated Short-Duration Power-Frequency Withstand Voltage | 20 kV, 28 kV, 36 kV, 38 kV, 50 kV |
| Rated Lightning Impulse Withstand Voltage | 60 kV, 75 kV, 95 kV, 95 kV, 125 kV |
| Rated Frequency | 50/60 Hz |
| Rated Normal Current | 400 or 630 A for ring-main feeders, 200 A for transformer feeders |
| Rated Filling Pressure | 1500 hPa (absolute) |
| Minimum Functional Pressure | 1300 hPa (absolute) |
| Ambient Temperature Range | -40°C to +70°C (without secondary equipment), -5°C to +55°C (with secondary equipment) |
The rated voltage range is 7.2 kV, 12 kV, 15 kV, 17.5 kV, and 24 kV.
The maximum rated lightning impulse withstand voltage is 125 kV.
The switchgear is available in 1200 mm, 1400 mm, and 1760 mm overall heights.
The minimum functional pressure is 1300 hPa (absolute).