Siemens NXAIR S Withdrawable Medium-Voltage Circuit-Breaker Product Leaflet


Siemens NXAIR S Withdrawable Medium-Voltage Circuit-Breaker Product Leaflet - cover page
Brand
Siemens
Document type
Product Leaflet
Language
English
Pages
30
File format
PDF
File size
2.8 MB
Published
16 March, 2012
Updated
16 March, 2012
MD5 checksum
146751120414DB293127F09F3E523961

About this manual

The Siemens NXAIR S is a withdrawable medium-voltage circuit-breaker switchgear designed for indoor installation up to 12kV, air-insulated. It features factory-assembled, type-tested metal-clad switchgear with modular design and maintenance-free vacuum circuit-breakers. The product is certified for universal application with high safety standards, including internal arc classification IAC A FLR and loss of service continuity category LSC 2B.

It is suitable for industrial and public power supply systems, including transformer and switching substations. Key benefits include modular compartment replacement, selective shutdown of arc faults, and reduced maintenance intervals over 10 years. The design saves space and cost while ensuring uninterrupted operation and personal safety.

What's inside

  • Application
  • Classification
  • Customer Benefits and Features
  • Technical Data
  • Dimensions
  • Room Planning
  • Standards
  • Components
  • Typical Uses

Specifications

Maximum Voltage12kV
Short-Circuit Breaking Current40kA
Internal Arc ClassificationIAC A FLR
Loss of Service Continuity CategoryLSC 2B
Partition ClassPM
Arc Duration1s
Degree of ProtectionIP4X

Frequently asked questions

What is the maximum voltage rating for the NXAIR S switchgear?

Up to 12kV, air-insulated.

Where is the NXAIR S circuit-breaker switchgear typically used?

It is used in transformer and switching substations, primarily at the primary distribution level.

What is the standard degree of protection for the NXAIR S?

The standard degree of protection is IP AX.

What are the maintenance intervals for the switchgear?

Maintenance intervals for the switchgear are greater than 10 years.

Download PDF (2.8 MB)