Yaskawa Varispeed E7 CIMR-E7B Error PUF: Fuse Blown

Yaskawa Varispeed E7 CIMR-E7B inverter · taken from the manufacturer’s manual, pages cited

Fault codePUF

Fuse Blown means a short circuit or ground fault on the inverter output side damaged the output transistors. The manual's first action is: “Investigate the cause, take corrective action, then replace the inverter.”

Model
Yaskawa Varispeed E7 CIMR-E7B
Display shows
Fuse Blown (PUF)
Type
Fault code
Source
Manual p. 181

What PUF means

Fuse Blown p. 255

Common causes

  • Fuse blown p. 255
  • Because of a short circuit or ground fault on the inverter output side, the output transistors are damaged. Check whether the following terminals are shorted. If shorted, it causes damage to the output transistors: B1(⊕3)→U,V,W ⊖→U,V,W. p. 255

What to do

  1. Investigate the cause, take corrective action, then replace the inverter. p. 255

Before you service the product, read the safety instructions in the manual p. 4.

If PUF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.

This page summarises what the manufacturer’s manual says about PUF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.