Overcurrent means a short circuit or ground fault on the inverter output side or load too large with acceleration time too short. The manual's first action is: “Investigate the cause and take corrective action, then reset. (Note) Before re‑energizing, be sure the inverter output side has no short circuit or ground fault.”
- Model
- Yaskawa Varispeed E7 CIMR-E7B
- Display shows
- Overcurrent (OC)
- Type
- Fault code
- Source
- Manual p. 181
What OC means
Overcurrent p. 255
Common causes
- Overcurrent p. 255
- A short circuit or ground fault on the inverter output side (caused by motor burnout, insulation degradation, cable damage leading to contact or ground short). p. 255
- Load too large. Acceleration time too short. p. 255
- Using a special motor or a motor exceeding the maximum applicable capacity. p. 255
- Opening or closing a contactor on the inverter output side. p. 255
What to do
- Investigate the cause and take corrective action, then reset. (Note) Before re‑energizing, be sure the inverter output side has no short circuit or ground fault. p. 255
Before you service the product, read the safety instructions in the manual p. 4.
If OC is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.
This page summarises what the manufacturer’s manual says about OC; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.