Heat sink overheating occurs when the inverter heat sink temperature exceeds the setting value of L8-02, there is a heat source nearby, or the inverter cooling fan has stopped running. The manual's first action is: “Ambient temperature is too high. Install cooling equipment.”
- Model
- Yaskawa Varispeed E7 CIMR-E7B
- Display shows
- oH
- Type
- Error code
- Source
- Manual p. 259
What oH means
Heat sink overheating: inverter heat sink temperature exceeds the setting value of L8-02. p. 259
Common causes
- Heat sink overheating: inverter heat sink temperature exceeds the setting value of L8-02. p. 259
- There is a heat source nearby. p. 259
- Inverter cooling fan has stopped running. p. 259
What to do
- Ambient temperature is too high. Install cooling equipment. p. 259
- Remove the heat source. p. 259
- Replace the cooling fan (contact the manufacturer). p. 259
Before you service the product, read the safety instructions in the manual p. 4.
If oH is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.
This page summarises what the manufacturer’s manual says about oH; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.