Yaskawa Varispeed E7 CIMR-E7B Error dnE: Run prohibited

Yaskawa Varispeed E7 CIMR-E7B inverter · taken from the manufacturer’s manual, pages cited

Error codednE

dnE means a RUN command is entered while the drive is in a prohibited (OFF) state with contact input set to 6A or 70. The manual's first action is: “Check wiring and external control signals.”

Model
Yaskawa Varispeed E7 CIMR-E7B
Display shows
Run prohibited (dnE)
Type
Error code
Source
Manual p. 260

What dnE means

Run prohibited p. 260

Common causes

  • Contact input is set to 6A (drive allowed) or 70 (bypass drive allowed) and a RUN command is entered while the drive is in a prohibited (OFF) state. p. 260

What to do

  1. Check wiring and external control signals. p. 260

Before you service the product, read the safety instructions in the manual p. 4.

If dnE is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.

This page summarises what the manufacturer’s manual says about dnE; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.