Yaskawa Varispeed E7 CIMR-E7B Error CPF01: Digital operator communication fault 2

Yaskawa Varispeed E7 CIMR-E7B inverter · taken from the manufacturer’s manual, pages cited

Fault codeCPF01

Digital operator communication fault 2 occurs when a communication fault lasting more than 2 seconds occurs after communication with the digital operator begins, or due to poor inverter control circuit operation or damage. The manual's first action is: “Poor jumper contact on the digital operator. Replace the inverter. Try turning the power off and on.”

Model
Yaskawa Varispeed E7 CIMR-E7B
Display shows
Digital operator communication fault 2 (CPF01)
Type
Fault code
Source
Manual p. 257

What CPF01 means

Digital operator communication fault 2 p. 257

Common causes

  • A communication fault lasting more than 2 seconds occurred after communication with the digital operator began. p. 257
  • Inverter control circuit is poor. p. 257
  • Control circuit damage. p. 257
  • Digital operator communication fault. p. 257

What to do

  1. Poor jumper contact on the digital operator. Replace the inverter. Try turning the power off and on. p. 257
  2. Replace the inverter. p. 257
  3. Please remove the operator and reinstall. p. 257

Before you service the product, read the safety instructions in the manual p. 4.

If CPF01 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Yaskawa service.

This page summarises what the manufacturer’s manual says about CPF01; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.