Vacon NXS/P Error 2: Overvoltage

AC drive · taken from the manufacturer’s manual, pages cited

Fault code2

Overvoltage happens when the DC-link voltage exceeds limits, often caused by too short deceleration time or high overvoltage spikes in the supply. The manual's first action is: “Set the deceleration time longer. Use the brake chopper or the brake resistor. They are available as options. Activate the overvoltage controller. Do a check of the input voltage.”

Model
Vacon NXS/P
Display shows
Overvoltage (2)
Type
Fault code
Source
Manual p. 150

What 2 means

Overvoltage p. 150

Common causes

  • The DC-link voltage is higher than the limits. p. 150
  • too short a deceleration time p. 150
  • high overvoltage spikes in the supply p. 150
  • Start/Stop sequence too fast p. 150

What to do

  1. Set the deceleration time longer. Use the brake chopper or the brake resistor. They are available as options. Activate the overvoltage controller. Do a check of the input voltage. p. 150

Before you service the product, read the safety instructions in the manual p. 13.

If 2 is still not resolved

  • Contact service or dealer for assistance. p. 13