The data address received in the query is not an allowable address for the server (or slave). The manual's first action is: “1. Use multi-meter to check whether the input voltage is within the specified limit. 2. Check the Parameter Cn012 if it is setting correctly. 3. If this alarm appears during operation. Extend ac/deceleration time or reduce load ratio in the permitted range. Otherwise, an external regeneration resistor is needed. (Please contact your supplier for assistance.)”
- Model
- TED TSTE Series
- Display shows
- ILLEGAL DATA ADD. (02)
- Type
- Error code
- Source
- Manual p. 179
What 02 means
ILLEGAL DATA ADD. p. 188
Common causes
- The data address received in the query is not an allowable address for the server (or slave). p. 188
- 1. The main circuit voltage is exceeded maximum allowable value. (410V) 2. Regeneration voltage is too high. p. 188
What to do
- 1. Use multi-meter to check whether the input voltage is within the specified limit. 2. Check the Parameter Cn012 if it is setting correctly. 3. If this alarm appears during operation. Extend ac/deceleration time or reduce load ratio in the permitted range. Otherwise, an external regeneration resistor is needed. (Please contact your supplier for assistance.) p. 188
If 02 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact TED service.